Model Predictive Direct Power Control of Four-Switch-Based Inverter Connected to Unbalanced Grid System
Typ dokumentu
stať ve sborníkuconference paper
Peer-reviewed
publishedVersion
Autor
Čerňan M.
Müller M.
Müller Z.
Tlustý J.
Valouch V.
Práva
closedAccessMetadata
Zobrazit celý záznamAbstrakt
A model based predictive direct power control with finite set of control variables for the three phase four-switch-based converter B4 connected to an unbalanced grid is introduced. The instantaneous active and non-active powers are outputs of the controlled system. The alternative instantaneous non-active power theory is used that preserves harmonic free grid currents not only for a symmetrical but also unsymmetrical voltage system. Simulation results for the L grid filter are presented and analyzed.
Zobrazit/ otevřít
Kolekce
- Publikační činnost ČVUT [1369]