Zobrazit minimální záznam



dc.contributor.authorDraxler K.
dc.contributor.authorStyblikova R.
dc.contributor.authorHlaváček J.
dc.contributor.authorRietveld G.
dc.date.accessioned2019-03-27T22:35:01Z
dc.date.available2019-03-27T22:35:01Z
dc.date.issued2018
dc.identifierV3S-326617
dc.identifier.citationDRAXLER, K., et al. Results of an International Comparison of Instrument Current Transformers up to 10 kA at 50 Hz Frequency. In: 2018 Conference on Precision Electromagnetic Measurements (CPEM 2018). Conference on Precision Electromagnetic Measurements (CPEM 2018), Paris, 2018-07-08/2018-07-13. Vail, Colorado: IEEE Instrumentation and Measurement Society, 2018. ISSN 2160-0171. ISBN 978-1-5386-0974-3. DOI 10.1109/CPEM.2018.8500821. Available from: https://ieeexplore.ieee.org/document/8500821
dc.identifier.isbn978-1-5386-0974-3 (online)
dc.identifier.issn2160-0171 (online)
dc.identifier.urihttp://hdl.handle.net/10467/81738
dc.description.abstractTraceability of the current ratio is crucial for the measurement of electrical energy in revenue metering. A comparison of the AC current ratio was therefore performed within EURAMET in the time period 2012-2016, using a precision CT as the traveling device. The Czech Metrology Institute (CMI) as coordinator processed the measurement results of the 15 European participating laboratories. The comparison of the results for transformer ratios of (4, 5, 6, 8, 10) kA 5 A at 15 VA burden and (4 and 10) kA 5 A ratios at 5 VA burden indicates good agreement between the participating laboratories. The main differences are found for phase displacement, at least in part due to instability of the traveling standard.eng
dc.format.mimetypeapplication/pdf
dc.language.isoeng
dc.publisherIEEE Instrumentation and Measurement Society
dc.relation.ispartof2018 Conference on Precision Electromagnetic Measurements (CPEM 2018)
dc.relation.urihttps://ieeexplore.ieee.org/document/8500821
dc.subjectcomparisoneng
dc.subjectcurrent measurementeng
dc.subjectCurrent ratioeng
dc.subjectcurrent transformers (CT)eng
dc.subjecthigh currentinstrumenteng
dc.subjecttransformerseng
dc.subjectphase displacementeng
dc.subjectratio erroreng
dc.titleResults of an International Comparison of Instrument Current Transformers up to 10 kA at 50 Hz Frequencyeng
dc.typestať ve sborníkucze
dc.typeconference papereng
dc.identifier.doi10.1109/CPEM.2018.8500821
dc.rights.accessclosedAccess
dc.identifier.wos000450231900036
dc.type.statusPeer-reviewed
dc.type.versionpublishedVersion
dc.identifier.scopus2-s2.0-85057026766
dc.relation.conferenceConference on Precision Electromagnetic Measurements (CPEM 2018)


Soubory tohoto záznamu


Tento záznam se objevuje v následujících kolekcích

Zobrazit minimální záznam