ANALYSIS OF THE INFLUENCE OF TRANSDUCER FREQUENCY ON THE ULTRASONIC MEASUREMENT OF CONCRETE HOMOGENEITY
Typ dokumentu
articlePeer-reviewed
publishedVersion
Autor
Kocáb, Dalibor
Misák, Petr
Jindrová, Barbora
Alexa, Martin
Vymazal, Tomáš
Práva
Creative Commons Attribution 4.0 International Licensehttp://creativecommons.org/licenses/by/4.0/
openAccess
Metadata
Zobrazit celý záznamAbstrakt
The paper analyses the influence of transducer frequency on the determination of concrete homogeneity using the ultrasonic pulse velocity test. Transit time measurements were made on a 590×590mm concrete slab, with 110mm in thickness, in a raster of 5×5 points, which means the slab was tested in 25 places. The tests were made using a Pundit PL-200 ultrasonic tester using transducers set at 54, 82, and 150 kHz. Two types of measurements were performed – spot measurements of the ultrasonic pulse transit time at each point and full area scanning. The paper is concluded by an evaluation of the concrete slab’s homogeneity measured by different transducers and techniques in addition to a statistical analysis of how the results are affected by the transducer frequency.